Previous Article Return to overview
Controler DULCOMETER® D2C cu doua canale

Controler DULCOMETER® D2C cu doua canale

Avantaje

  • Universal, pentru masura si controlul combinat al numeroase variabile: pH / Redox, pH/ clor, pH/ pH, pH/ Dioxid de clor şi clor/ clor
  • Ideal adaptat cerintelor procesului datorita numeroaselor trepte de extensie
  • Integrare facila in procesul tehnologic: multiple posibilitati de instalare a senzorilor si de control al echipamentelor de dozare
  • Procese optimizate datorita functiunilor speciale precum dozare in sarcina de baza, multiple functiuni de valoare limita.
  • Siguranta: monitorizarea valorii limita cu temporizare la dozare.
  • Usor de operat, prin intermediul afisajului grafic si al meniului in 8 limbi.
  • Afisaj grafic generos pentru valori masurate, valori de corectie si informatii.

Controlerul cu doua canale DULCOMETER® D2Ceste un dispozitiv de masura si control bazat pe thenologia cu microprocesor si care ofera un inalt grad de fiabilitate intr-un spectru latg de aplicatii. Controlerul este configurabil si, prin urmare, poate fi adaptat pentru a satisface nevoile dumneavoastra specifice. Cerinta aplicabula tipului de control, tipului constructiv (montaj pe perete, pe panou etc.) precum si altor parametri. Dumneavoastra specificati de ce aveti nevoie si platiti doar pentru atat.

Applications for measured quantity combinations pH/Redox, pH/Chlorine and Chlorine/Chlorine

  • Water treatment for swimming pools
  • Differentiating measurement of Chlorine, reduction of combined Chlorine in swimming pool water purification
  • Cooling water treatment

Application for measured quantity combination pH/pH

  • Effluent treatment
  • Neutralisation
  • All applications have to be fitted with a redundant pH measuring device for safety reasons

Application for measured quantity combination pH/Chlorine dioxide

  • Combating legionella
  • Drinking water treatment

Features

  • Threshold value monitoring with adjustable automatic cut-out as standard
  • Probe connection in two-wire technology, unaffected by interference
  • 2 signal outputs 0/4 – 20mA galvanically separated
  • Different designs for wall and panel mounting
  • 1 digital input for pause and error monitoring of sample water
  • 1 digital input for super chlorination or basic load
  • Basic load dosing (additive effect)
  • Unidirectional control for pH/Redox, pH/Chlorine dioxide and pH/Chlorine, bidirectional control for pH/pH
  • Neutral zone control for pH/pH
  • Temperature compensation for pH
  • Chlorine difference measurement for Chlorine/Chlorine
  • Regulating output for minimising combined chlorine for Chlorine/Chlorine

Technical Data

Measurand Value
Accuracy 0,5 % of measuring range
Correction variable Temperature via Pt 100
Correction range 0...100°C
Control modes P, PI, PD, PID
Control

Bidirectional control with pH/pH

Unidirectional control with pH/Redox, pH/Chlorine dioxide and pH/Chlorine

Dead zone control with pH/pH

Basic load (additive effect)

Manual adjustment variable for test purposes

Adjustable outputs

2 Reed contacts (pulse frequency output)

2 power relays (pulse length) or

2 Analogue outputs (0/4...20 mA)

Analogue outputs

2 analogue outputs ((0/4…20 mA) galvanically separated, max load 600 W(2. Output 400W) Assignable as measurement, correcting or variable adjustment mode.

Alarm relay 250V ~3 A, 700 VA, changeover contact type
Electrical connection 24 V AC/DC / 100 V~ / 115 V~ / 200 V~ /230 V~ ±10%
Protection class

Wall mounted: IP 65

Panel mounted: IP 54

Ambient temperatures

Wall mounted: -5..0.40°C (non-condensing)

Panel mounted: 0..0.40oC (non-condensing)

Dimensions in mm (WxHxD)

Panel mounted: 96 x 96 x 140 mm

Wall mounted: 189 x 200 x 76

Measurand Measurement and Control Range  Resolution Measuring input
pH (measured quantity 1) 0 - 14 0,01pH Input resistance > 1012 W or terminal standard signal 0/4...20 mA
Redox (measured quantity 2) 0 - 1000 mV 1 mV Terminal standard signal 0/4...20 mA
Chlorine (measured quantity 2)

0,05 - 0,500 ppm
0,05 - 2,00 ppm
0,05 - 5,00 ppm
0,05 - 10,00 ppm
0,05 - 20,00 ppm
0,05 - 50,00 ppm
0,05 - 100,00 ppm 

0,001 ppm
0,01 ppm
Terminal standard signal 0/4...20 mA

ProMinent DULCOMETER® Measuring and Control system uses DULCOTEST® sensors and ProMinent dosing pumps to build a complete control system with measurement, control, dosage and recording, all from one source and optimised to work together.